Short answer: For backup, battery capacity (kWh) ≈ critical load (kW) × backup hours ÷ usable depth of discharge ÷ inverter efficiency. A 2 kW critical load for 6 hours at 90 % depth of discharge needs about 14.5 kWh. The inverter must deliver the continuous load plus motor start-up surges.

How to use the result

The calculator gives a first estimate. Before ordering, our engineers also check:

Factor Why it matters
Surge loads Motors and compressors need 3–6× running power for a moment
Temperature Batteries deliver less in cold and age faster in heat
Recharge The solar array must refill the battery between outages
Growth Adding loads later is cheaper if the inverter is sized for it now

Example

A shop runs lights, a fridge, a till and Wi-Fi — about 1.5 kW — and faces 4-hour evening outages. 1.5 × 4 ÷ 0.9 ÷ 0.92 ≈ 7.2 kWh, so a 51.2 V battery bank of about 7.5–10 kWh with a 3–5 kW hybrid inverter is a sensible start.